Flexible Current Transformers up to 3000 A
Electrical Characteristics
| Measurement range: | 30 / 300 / 3000 A ACRM |
| Output Sensitivity: | 100 mV / 10 mV / 1 mV per A |
| Load impedance: | 100 kΩ minimum |
| Noise: | 8 mV (30 A) / 2 mV (300 / 3000 A) |
| Accuracy: (at 25 °C) |
± 1 % of range (45 Hz … 65 Hz) |
| Bandwidth: (-3 dB) |
10 Hz … 50 kHz |
| Phase erro: (45 Hz … 65 Hz) |
± ≤ 1° |
General Characteristics
| Probe length: | 610 mm |
| Conductor diameter: | 194 mm |
| Probe diameter: | 9.9 mm (nominal) |
| Output connection: (7 core cable / 2 m long) |
Redel-plug |
| Operating temperature: | -20 … +80 °C |
| Storage temperature: | -40 … +90 °C |
| Degree of protectio: | Probe (IP 65) Integrator module ( IP 4x) |